Skip to content
All Building Knowledge topics

BACnet/MS/TP termination

CURRENTSAFEPRODUCT CLAIM: SAFEINDEX: INDEXABLE
Answer

BACnet/MS/TP RS-485 networks require 120Ω termination resistors at both ends of the trunk cable to prevent signal reflections and ensure communication reliability.

Why It Matters

This matters in these Alpha Controls workflows: bms-network-install, commissioning-check.

Relevant GUVNR Workflows
  • bms-network-install
  • commissioning-check
Evidence & Provenance
Source
ASHRAE Standard 135-2020; CIBSE TM-23
Provenance
first-hand
Last reviewed
2024-03-15
Review cycle
3 years
Need a governed answer for your building?
Talk to an Alpha Controls engineer about your BMS, HVAC controls, and managed instrumentation needs.