Trend BMS upgrades, maintenance and support
IQ3 and IQ4 systems moved onto IQ5, 963 supervisors moved onto IQVISION, and existing Trend sites kept running across London, Kent and the South East.
We are an independent contractor, not a Trend partner. We work on the Trend system you already have, whoever put it in, and hand back everything you need to own it.

Where Trend is now: the IQ5 family
Trend launched IQ5 in November 2023, its fifth generation of IQ controller. The big changes are a T1L Ethernet I/O bus (10 Mbit/s, up to 300 m between modules), encrypted and authenticated communications, and a single site login synchronised across every controller. IQ5 is designed to the ISA/IEC 62443-4-2 security standard for industrial control system security.

Supervisors, displays and tools
Controllers are engineered with IQSET (version 8.00 or later for IQ5). Above them, IQVISION has replaced the 963 as Trend's supervisor.
What most buildings are actually running
Most Trend sites we see are not on IQ5 yet. They run IQ4 controllers, IQ3 and XCITE controllers that Trend withdrew years ago, and often a 963 supervisor on an ageing PC.
- IQ4 — the generation most commercial buildings run today, including the IQ4E Ethernet controllers that replaced the IQ3. Serviceable, and a sound base to extend from.
- IQ3 / XCITE — withdrawn from sale. Often still working, but spares get harder every year. Our Trend end-of-life register lists withdrawal dates and replacements model by model.
- 963 supervisor — Honeywell withdrew all support at the end of 2024; a third-party industry source puts its removal from sale at December 2019 and the end of relicensing at January 2024. A dead PC can mean a supervisor you cannot relicense.
From our own work: IQ3 XCITE out, IQ5 in
We were contracted for the rip-out and retrofit on this panel: an IQ3 XCITE controller and XCITE I/O replaced with an IQ500 and IQ5 I/O modules, with the existing field wiring labelled and transferred. The physical swap took about eight hours. The hardware was supplied by others and the design was not ours — this was installation work.


What to know before an IQ5 job
From Trend's own release notes and from engineers working on IQ5 in the field.
What we do on Trend sites
- IQ3 and IQ4 to IQ5 controller replacements, keeping existing field wiring where it is sound
- 963 to IQVISION supervisor migrations, including graphics, alarms, schedules and trend logs
- Planned maintenance, fault-finding and strategy repairs on IQ2, IQ3, IQ4 and IQECO systems
- New Trend control panels designed, built and wired in-house
- IQ5 firmware upgrades, account set-up and secure handover of the site admin account
- BACnet, Modbus and M-Bus integration of chillers, boilers, VRF and metering
- Strategy and network health checks on Trend systems we have inherited from others
- Electrical, containment and cabling for controls work under the same contract
Integration
An IQ5 is a BACnet Building Controller over IP. Its RS-485 ports can each run Modbus, M-Bus, BACnet MS/TP or XNC, and it reads Modbus devices over IP too. Modbus, M-Bus and XNC are enabled with an integration licence, so they need to be in the order, not discovered at commissioning.
Where a site mixes Trend with other manufacturers, IQVISION and the TONN9 bring the systems under one front end. Our guide to getting Distech and Trend to talk over BACnet covers the usual network problems.
Why use Alpha Controls on a Trend site
- Engineers who hold Trend training certificates, working on IQ3, IQ4 and IQ5
- Independent — we are not tied to a manufacturer, so we can tell you when IQ4 is still the right answer
- Panels designed and built in-house, with electrical, cabling and controls under one contract
- You get the strategy files, backups and the IQ5 admin account at handover
- BCIA member, SafeContractor accredited, Constructionline Gold
- Based in Gravesend, covering London, Kent and the South East
Trend BMS by region
Frequently asked questions
Are Alpha Controls an approved Trend installer or Trend partner?
No. Alpha Controls is an independent BMS contractor. We do not hold Trend or Honeywell partner status and we are not a Trend approved installer. Our engineers do hold Trend training certificates. We work on Trend systems whoever installed them, and we are clear about that from the first conversation.
What is the latest Trend controller?
The IQ5 family. Trend launched IQ5 in November 2023 with the IQ500 modular controller, and has since added the IQ528 equipment controller (data sheet June 2025) and the IQ5ECO unitary range (first firmware release V2.30). IQ5 adds a 10 Mbit/s T1L I/O bus, end-to-end encrypted communications and a design aimed at the ISA/IEC 62443-4-2 security standard.
Can an IQ5 reuse our existing IQ3 or IQ4 I/O modules?
Yes, within limits. The IQ5 has a separate IQ3/4 I/O bus, enabled with a CAN licence, that takes up to 30 IQ4/IO modules, or 15 where XCITE (IQ3) modules are used. Those modules need their own 24 V DC supply. Old IQ1 to IQ4 strategies can be imported into IQSET and converted to IQ5 strategies, but they still need checking line by line before they go live.
Should we upgrade from IQ3 to IQ4 or straight to IQ5?
It depends on the site. If the IQ3 I/O and field wiring are in good condition, an IQ5 on the IQ3/4 bus can replace the processor while keeping the I/O, then the I/O can be replaced in phases. If the site already runs a large IQ4 estate and the team has no IQ5 experience, staying on IQ4 for now can be the lower-risk option. We set out both routes with prices before you commit.
Is the Trend 963 supervisor still supported?
No. Honeywell withdrew all support for the 963 at the end of 2024 (31 December 2024). A third-party industry source also reports that it was removed from sale in December 2019 and that relicensing stopped on 1 January 2024. The main risk is that a PC failure or host change leaves a 963 that cannot be relicensed. IQVISION is the replacement.
Will an IQ5 work on our existing Trend network?
Yes. Trend states the IQ528 can coexist with IQ1, IQ2, IQ3, IQ4 and IQECO controllers on the same Trend network, and the IQ5 can join an existing internetwork. Firmware upgrades still need an IP connection to each IQ5, so we check the network before quoting.
Got a Trend system that needs attention?
An IQ3 on borrowed time, a 963 nobody can log into, or a plan to move to IQ5 — send us what you have and we will come back with options and prices.