Trend controller end-of-life register

Withdrawal dates, published replacement controllers and support-window dates for withdrawn Trend IQ controllers and the 963 supervisor. Every row is cited, and every derived date shows the interval it was derived from.

19 entries · sources last checked 28 August 2026

All 18 controllers in the published withdrawal table are now past Trend’s stated ten-year support horizon.

The last of them — IQ221/223/228/229 and the IQ3XCITE and IQ3XACT XNC variants — was withdrawn on 30 April 2016 and passed the ten-year mark on 30 April 2026. The 963 supervisor is counted separately: its support dates were announced by the vendor rather than derived from the policy interval, and its own ten-year point has not yet arrived even though technical support ended on 1 January 2025. This describes the products in the published withdrawal record only. IQ4-series products are not in that record.

How the support dates are worked out

Trend publishes support intervals as a policy rather than per-product end dates. Applying that policy to each withdrawal date gives the dates in the table. The intervals, quoted from the source:

18 months

after withdrawal, regular security updates discontinue

2 years

after withdrawal, fixes for critical functionality anomalies end

10 years

after withdrawal, the reasonable-endeavours support commitment ends

“Regular security updates will discontinue, effective 18 months following the withdrawal date, and continued use of these products will not be supported thereafter from a security perspective.”

The register

ControllerWithdrawnPublished replacementSupport statusSource
IQ250IQ1/IQ2 seriesMarch 200521 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: September 2006 *
  • Critical functionality fixes ended: March 2007 *
  • End of ten-year support commitment: March 2015 *
epa-2017single-source
IQ21x (230V)IQ1/IQ2 seriesJune 201214 years ago
  • IQ41x/LAN/230

The source presents the LAN cable extender and IQ41x adaptor plate note once against the merged IQ21x pair, so it applies to both the 230V and 24V rows.

Past 10-year support horizon
  • Security updates discontinued: December 2013 *
  • Critical functionality fixes ended: June 2014 *
  • End of ten-year support commitment: June 2022 *
epa-2017single-source
IQ21x (24V)IQ1/IQ2 seriesDecember 201213 years ago
  • IQ41x/LAN/24VAC
  • Consider LAN cable extender and IQ41x adaptor plate
Past 10-year support horizon
  • Security updates discontinued: June 2014 *
  • Critical functionality fixes ended: December 2014 *
  • End of ten-year support commitment: December 2022 *
epa-2017single-source
IQ246IQ1/IQ2 seriesDecember 201213 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: June 2014 *
  • Critical functionality fixes ended: December 2014 *
  • End of ten-year support commitment: December 2022 *
epa-2017single-source
IQ222 (24V & 230V)IQ1/IQ2 seriesJune 201313 years ago
  • IQ422/12/LAN/230
  • IQ422/12/LAN/24VAC
Past 10-year support horizon
  • Security updates discontinued: December 2014 *
  • Critical functionality fixes ended: June 2015 *
  • End of ten-year support commitment: June 2023 *
epa-2017single-source
IQ3xactIQ3 seriesJune 201313 years ago
  • IQ422/12/xx/230
  • IQ422/12/xx/24VAC
Past 10-year support horizon
  • Security updates discontinued: December 2014 *
  • Critical functionality fixes ended: June 2015 *
  • End of ten-year support commitment: June 2023 *
epa-2017single-source
IQ231IQ1/IQ2 seriesJuly 201313 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: January 2015 *
  • Critical functionality fixes ended: July 2015 *
  • End of ten-year support commitment: July 2023 *
epa-2017single-source
IQ241IQ1/IQ2 seriesJuly 201313 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: January 2015 *
  • Critical functionality fixes ended: July 2015 *
  • End of ten-year support commitment: July 2023 *
epa-2017single-source
3XTEND (EINC L)Network interfaceSeptember 201313 years ago
  • XTEND/24V or IQ4NC/00/230
  • ENCLS/MBOX/XTEND & ACC/24VAC
Past 10-year support horizon
  • Security updates discontinued: March 2015 *
  • Critical functionality fixes ended: September 2015 *
  • End of ten-year support commitment: September 2023 *
epa-2017single-source
EINCNetwork interfaceDecember 201312 years ago
  • XTEND/24V or IQ4NC/00/230
Past 10-year support horizon
  • Security updates discontinued: June 2015 *
  • Critical functionality fixes ended: December 2015 *
  • End of ten-year support commitment: December 2023 *
epa-2017single-source
IQ241 S CardsIQ1/IQ2 seriesSeptember 201412 years agoNone published — controller-level change required

Source lists no replacement part. Migration requires a controller-level change.

Past 10-year support horizon
  • Security updates discontinued: March 2016 *
  • Critical functionality fixes ended: September 2016 *
  • End of ten-year support commitment: September 2024 *
epa-2017single-source
IQ233 (all variants)IQ1/IQ2 seriesMarch 201610 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: September 2017 *
  • Critical functionality fixes ended: March 2018 *
  • End of ten-year support commitment: March 2026 *
epa-2017single-source
IQ251 (all variants)IQ1/IQ2 seriesMarch 201610 years ago
  • IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements

Source notes I/O cards remained available at time of publication (August 2017).

Past 10-year support horizon
  • Security updates discontinued: September 2017 *
  • Critical functionality fixes ended: March 2018 *
  • End of ten-year support commitment: March 2026 *
epa-2017single-source
IQ221, IQ223, IQ228, IQ229IQ1/IQ2 series30th April 201610 years ago
  • IQ422/12/LAN/… or IQ4E/xx/LAN/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: October 2017 *
  • Critical functionality fixes ended: April 2018 *
  • End of ten-year support commitment: April 2026 *
epa-2017single-source
IQ3XCITE/xx/100-240IQ3 series30th April 201610 years ago
  • IQ4E/xx/xx/BAC/230
  • IQ4/IO modules to match I/O requirements
Past 10-year support horizon
  • Security updates discontinued: October 2017 *
  • Critical functionality fixes ended: April 2018 *
  • End of ten-year support commitment: April 2026 *
epa-2017single-source
IQ3XACT/12/XNCIQ3 series30th April 201610 years ago
  • IQ422/12/XNC/xx/BAC/xx
Past 10-year support horizon
  • Security updates discontinued: October 2017 *
  • Critical functionality fixes ended: April 2018 *
  • End of ten-year support commitment: April 2026 *
epa-2017single-source
IQ3XCITE/00/XNCIQ3 series30th April 201610 years ago
  • IQ422/00/XNC/xx/BAC/xx
Past 10-year support horizon
  • Security updates discontinued: October 2017 *
  • Critical functionality fixes ended: April 2018 *
  • End of ten-year support commitment: April 2026 *
epa-2017single-source
IQ3XCITE/96/XNC/xx/100-240IQ3 series30th April 201610 years ago
  • IQ4E/96/XNC/xx/BAC/230
Past 10-year support horizon
  • Security updates discontinued: October 2017 *
  • Critical functionality fixes ended: April 2018 *
  • End of ten-year support commitment: April 2026 *
epa-2017single-source
963 SupervisorSupervisorDecember 2019 (removed from sale)6 years ago
  • IQVISION Supervisor

The 963 has vendor-announced lifecycle dates, so the policy-derived intervals do not apply. Loss of relicensing is the material risk: a hardware failure or host change can leave the supervisor unrecoverable.

Vendor support ended (announced)
  • Relicensing withdrawn: January 2024
  • Technical support ended: January 2025
robinsons-2023honeywell-963-iqvisionsingle-source

* Derived by applying Trend’s published support intervals to the withdrawal date. These are not dates Trend announced for that individual product. Dates without an asterisk were announced for that product directly.

What “past the ten-year horizon” does and does not mean

The dates above describe Trend’s stated support position. They are not a verdict on the hardware in your building, and it is worth being precise about the difference.

What it does mean

  • The product is past the period Trend stated it would use reasonable endeavours to support, so a replacement or exchange after a field failure is no longer something you can rely on.
  • Regular security updates stopped 18 months after withdrawal. On the 30 April 2016 cohort that was October 2017.
  • Spares depend on whatever stock and repair capacity still exists, which is a commercial question rather than a supported one.
  • It is a planning signal: failure of an unsupported controller becomes a programme risk rather than a maintenance event.

What it does not mean

  • It does not mean the controller has stopped working. Plenty of these units are running correctly today and will continue to.
  • It does not mean support is unavailable in every circumstance — Trend’s wording is reasonable endeavours subject to parts availability, not a hard cut-off, and integrators still service these systems.
  • It does not create any legal or regulatory obligation to replace the equipment.
  • It is not a safety finding. Nothing here says the equipment is unsafe.
  • It does not mean the controller is incompatible with a modern system. Migration paths exist, and field wiring can usually be reused.
Withdrawn Trend IQ3 XCITE controller and I/O in a control panel
Before: a withdrawn IQ3 XCITE controller and I/O.
The same panel after replacement with a Trend IQ500 controller and IQ5 I/O
After: IQ500 and IQ5 I/O, fitted by our team. Read the retrofit write-up

What to do next

  1. Establish what you actually have. Controller type and count per plant room, taken from the system rather than from the O&M file, which is frequently out of date. The register is only useful against a real inventory.
  2. Separate risk from age. A withdrawn controller on non-critical plant is a different proposition from the same controller running a landlord LTHW system or a data hall. Rank by consequence of failure, not by withdrawal date.
  3. Check the supervisor separately. On a 963 the binding constraint is usually relicensing rather than hardware — a host change or disk failure can leave the licence unrecoverable.
  4. Plan a phased migration, not a rip-out. Replacement is normally staged across budget years, taking the highest-consequence plant first and reusing field wiring where it is sound.
  5. Confirm the position for your own estate. These dates come from the sources cited below, not from an inspection of your site. Verify with Trend or your maintainer before committing spend.

Common questions

Is my Trend IQ3 controller still supported?

Every IQ3 variant in the published withdrawal record was withdrawn on or before 30 April 2016. Applying Trend's stated ten-year support commitment to those withdrawal dates, the last IQ3 cohort passed that horizon on 30 April 2026. Trend's stated 18-month security-update window for the same cohort closed in October 2017. That does not mean the controller has stopped working — it means replacement or exchange after a field failure can no longer be relied on.

What replaces a Trend IQ3xcite controller?

The source lists the suggested replacement for IQ3XCITE/xx/100-240 as the IQ4E/xx/xx/BAC/230 with IQ4/IO modules matched to the I/O requirement, and IQ3xact as IQ422/12/xx. These are the replacements the published table suggests rather than formally designated successors, so confirm the specific mapping for your site before ordering.

When did the Trend 963 supervisor lose support?

Honeywell withdrew all support for the 963 at the end of 2024 (31 December 2024). The cited third-party source (an FM provider's article, not a Trend publication) also records that it was removed from sale in December 2019 and that relicensing was withdrawn on 1 January 2024. Those dates were announced for the product rather than derived from the ten-year policy interval, so the 963 is listed separately from the withdrawal-table cohort. The practical risk is relicensing: after a hardware failure or host change the licence may not be recoverable.

Sources, and what this register does not cover

Read this before you rely on a date.

The withdrawal table is reproduced from a Trend partner publication dated August 2017. We have not located the underlying Trend or Honeywell bulletin, so every withdrawal date here is single-source and accurate as at August 2017. Products withdrawn after that date are not in the table — the 963 supervisor is included separately from its own source.

Support intervals are subject to the availability of component parts, and Trend states the ten-year commitment as reasonable endeavours rather than a guarantee. Confirm the position for your own estate with Trend or your maintainer before making a spend decision.

  1. epa-2017UPGRADE TODAY! — Trend IQ4 upgrade flyer, incorporating 'Your obsolescence checklist'

    Environmental & Process Automation Ltd (EPA Ltd), Co. Kildare, Ireland · published 2017-08 · retrieved 2026-08-28 · partner-published

    A Trend partner reproducing Trend Control Systems withdrawal data and Trend's own support-policy wording. It is NOT a Honeywell/Trend primary publication, and we have not located the underlying Trend bulletin. Treat the dates as accurate to August 2017 and unverified since.

    View source
  2. robinsons-2023Trend BMS — Is Your Building Management System Up To Date?

    Robinsons Facilities Services · published 2023-10-06 · retrieved 2026-08-28 · third-party

    Last updated 2026-06-05. An FM provider, not a Trend partner — the tier says third-party because nothing in the article claims a Trend partnership. It attributes the 963 dates to Trend; we have not located a Trend-published notice carrying them.

    View source
  3. honeywell-963-iqvision963 -> IQVISION (963 to IQVISION upgrade licences)

    Honeywell Building Automation (Trend) · published 2023-08 · retrieved 2026-11-01 · primary

    Manufacturer product page. Verbatim: "we will be withdrawing ALL support for the 963 Supervisor at the end of next year, 31/12/2024." Undated; 2023-08 is inferred from the upgrade scheme it describes ("from 1st Aug 2023 until … 31st Dec 2023"). It does NOT state the December 2019 removal from sale or the January 2024 relicensing date — those rest on robinsons-2023 (third-party) only.

    View source