Skip to content
Energy Management

How to Reduce Commercial Building Energy Costs with a BMS

By Alpha Controls Team | 18 February 2026 | 10 min read

A correctly configured building management system can cut commercial building energy costs by 10–20%, mostly through software changes alone. UK commercial buildings waste 20–40% of the energy they consume on plant running outside occupied hours, simultaneous heating and cooling, and control sequences never re-tuned since original commissioning.

Why do commercial buildings waste so much energy?

The average commercial building in the UK wastes between 20% and 40% of the energy it consumes. The causes are consistent across building types: plant running on default settings, heating and cooling fighting each other, systems operating outside occupied hours, and control sequences never updated since original commissioning years ago.

The good news is that most of this waste is recoverable without capital investment in new plant. A well-configured building management system can recover the majority of it through software changes and reconfiguration.

How do BMS schedules cut energy costs?

The single most common source of wasted energy in commercial buildings is plant running outside occupied hours. HVAC systems should only run when people are in the building, with a pre-heat or pre-cool period of 30–60 minutes before occupation begins — not from midnight.

Check your BMS schedules against actual building use. If the building is occupied 08:00–18:00 Monday to Friday but the BMS schedule shows 06:00–22:00 seven days a week, you are paying for 16 extra hours of HVAC operation every weekday and a full weekend of unnecessary heating or cooling. On a medium office building, correcting schedules alone can save £5,000–£15,000 per year.

Ensure bank holidays and seasonal shutdowns are programmed. Most BMS systems have calendar override features that are rarely used.

What is simultaneous heating and cooling, and how do you stop it?

Simultaneous heating and cooling — where the heating system and cooling system both run at the same time in the same zone — is extremely common in buildings with poorly sequenced plant and is often invisible to facilities managers unless the BMS is specifically configured to flag it.

On mild days, air conditioning and heating can run simultaneously for hours. In buildings with four-pipe fan coil systems, individual FCUs can be simultaneously heating and cooling adjacent zones. The fix is correctly configured dead bands in the control sequence — a temperature range within which neither heating nor cooling is active — and proper inter-lock logic between heating and cooling plant at the BMS level.

Ready to discuss your building? Request a free BMS survey →

What is optimum start on a BMS?

Optimum start is a BMS function that calculates the latest possible start time for HVAC plant to reach target conditions by the beginning of occupied hours, based on the current building temperature and the outside air temperature. It replaces fixed early-morning start times with a dynamic calculation.

On a mild spring morning, a building may reach setpoint by starting 20 minutes before occupancy. On a cold winter morning, it might need 90 minutes. Optimum start ensures the building is always ready on time while never running plant longer than necessary. Buildings without optimum start typically use a fixed start time sized for the worst case — which means they over-run for most of the year.

Most modern BMS controllers support optimum start as a built-in function. If it's not enabled on your system, ask your BMS contractor to activate it — it is one of the lowest-cost, highest-return changes available.

What is night setback and frost protection?

Rather than turning heating completely off overnight, night setback maintains a reduced temperature setpoint — typically 12–16°C — to avoid the building getting so cold that the morning pre-heat period extends into occupied hours. This is more energy efficient than turning heating completely off in cold weather, because the energy to reheat a very cold building over several hours exceeds the energy saved by running at a lower setback.

Frost protection is a separate function that prevents pipework freezing in unheated spaces. It should be enabled specifically for plant rooms, roof-level plant, and any areas where pipework is exposed to outside temperatures. Combined with trace heating systems for vulnerable external pipework, frost protection prevents the kind of burst pipe damage that can cost tens of thousands of pounds to repair.

How does free cooling save energy?

Free cooling — also called economiser control — uses outside air for cooling when outside temperatures are below inside temperatures. Instead of running the mechanical refrigeration circuit, the AHU opens its outside air damper to bring in cool air directly. On a 14°C day in March, you can cool a building entirely for free while the chiller sits idle.

Most air handling units have the physical hardware to support free cooling — the dampers and mixing boxes are already there. The question is whether the BMS control sequence is written to take advantage of it. Many are not. Enabling free cooling typically requires changes to the AHU sequence in the BMS controller and is one of the highest-value software changes available on older systems.

How do variable speed drives reduce BMS energy use?

Variable speed drives (VSDs) reduce fan and pump motor speed — and therefore energy consumption — when full capacity is not required. A fan running at 80% of full speed consumes only 51% of the energy of the same fan at full speed (following the cube law). But VSDs only save energy when they're actually varying speed — which requires correctly configured BMS control.

Common problems: VSDs set to run at a fixed speed rather than responding to duct pressure or flow demand; BMS setpoints left at design maximum rather than adjusted for actual building loads; VSD faults not flagged to the BMS and therefore unnoticed for months. For the full set of HVAC control sequences these fixes sit within — duct pressure reset, dead bands, chiller and boiler sequencing — see our guide to HVAC controls integration best practices.

What is demand-controlled ventilation and when is it worth fitting?

Demand-controlled ventilation (DCV) varies the fresh air rate with occupancy instead of supplying the design maximum all day. A CO2 sensor in the space or the extract duct tells the BMS how heavily the room is occupied, and the BMS modulates the outside air damper or the fan speed to hold a CO2 setpoint. Outside air that is not brought in does not have to be heated or cooled.

It pays most where occupancy swings: meeting rooms, lecture theatres, halls, and open-plan floors that are half empty on some days. It does little in a space that is full all day. The sequence needs a minimum fresh air position that still meets the ventilation design, and the CO2 sensors need checking against a reference at each service visit, because a sensor that drifts low will under-ventilate the room without raising an alarm. Our guide to CO2 monitoring and indoor air quality on a BMS covers sensor placement and setpoints.

Should lighting be linked to the BMS?

Lighting usually has its own control system, but linking it to the BMS removes two common sources of waste. The first is lights left on in empty areas: occupancy sensors switch them off, and the same occupancy signal can set back the heating and ventilation for that zone. The second is fittings at full output beside a window on a bright day: daylight dimming trims the fittings nearest the glazing to hold a set light level.

An LED upgrade is the time to do this. Specify dimmable, DALI-addressable drivers as part of the upgrade, and ask for the lighting control system to expose occupancy and status to the BMS over BACnet or a DALI gateway. The time schedules then live in one place, and the FM team can see lights running out of hours on the same screen as the plant.

Why does BMS energy metering matter for compliance?

You cannot manage what you cannot measure. BMS-integrated energy metering breaks down energy consumption by system, floor, or tenant — identifying the largest consumers and tracking the impact of optimisation changes. Electricity sub-meters on each HVAC circuit will quickly show whether an AHU is using significantly more energy than expected, which typically indicates a mechanical fault, an incorrect VSD speed, or a control strategy problem.

Half-hourly interval data from BMS-integrated meters directly supports several compliance obligations that affect UK commercial landlords. Under MEES, properties must meet Band E today, and under the June 2026 interim response, buildings over 1,000 m² are expected to reach EPC B by 2031, with the previously proposed interim C milestone dropped. ESOS Phase 3 (the compliance cycle running to December 2027) requires qualifying organisations to audit energy consumption across their estate — metered building data significantly reduces the cost and effort of that exercise. BREEAM In-Use credits for energy monitoring depend on having demonstrable interval data from installed meters, not estimates. Getting the metering infrastructure in place now, integrated with the BMS, is considerably cheaper than retrofitting it under compliance pressure.

What is BMS energy recommissioning and what does it save?

For buildings with an existing BMS that has never been re-tuned since original commissioning, energy recommissioning is typically the highest-return intervention available. Alpha Controls carries out BMS energy audits that identify wasted energy, misconfigured sequences, and disabled optimisation functions — and then implements the changes required to recover that waste.

A recommissioning project typically costs £5,000–£20,000 depending on system size and delivers 10–20% energy savings, often paying back within 12 months.

If your building has been running the same BMS for more than three years without any controls review, a recommissioning audit will almost certainly identify significant savings. Contact Alpha Controls to arrange an energy audit across London, Kent, Essex, and across the South East.

Published by Alpha Controls Team, 18 February 2026

Recommended Articles

Need Expert Advice?

Our team of building automation specialists is ready to help you optimise your building's performance and efficiency.

Get in Touch